A complete diesel generator set including the diesel engine, alternator, control panel, automatic starting equipment, fuel tank and all other accessories for autonomous operation
Rates power: 150kVA, 120kW, Power factor (Cos. phi = 0.8), 400/230V, 3-phase, 50 Hz at NTP (Normal Temperature and Pressure)
The use of the generator as prime or stand-by should be clearly stated by the country office when the set is requested
Engine:
Water-cooled with fresh water loop and tropical radiator
Synchronous speed: Up to 1500rpm
Mechanical speed governor
Heavy duty air cartridge filter
Cartridge oil filter
External fuel filter
Industrial silencer
Exhaust with suitable flexible piping
Automatic electric starter including batteries, leads and automatic battery charging equipment
Alternator:
Synchronous and brushless
Automatic fast voltage regulator, maintaining the output within 2% under normal conditions
Screen protected
Fuel tank:
Fuel tank of suitable construction with capacity sufficient to run the generator set continuously for 8 hours at the rated capacity
Suitable piping should be provided for connecting the tank to the engine as well as for filling the tank
Fuel level indicator should be placed conveniently on the panel board
Panel board:
Made of steel sheets of appropriate thickness subjected to anti-oxidizing treatment and covered with epoxy resin with suitable protection factor
The panel board comprises:
Automatic main circuit breaker
Change over switch with positions for "MAINS" - "OFF" - "GENERATOR"
Key to start and stop the unit
Emergency stop button
Set-point for speed/governor control
Set-point for voltage control
Protection:
The generator set should be equipped with automatic shutdown equipment if fatal parameters are exceeded including low oil pressure, high engine temperature and over-speed
Mounting:
The engine and the alternator should be connected with a heavy-duty elastic coupling and should be mounted on a common rigid base frame with anti-vibration dampers and lifting eyes flexible for transportation
Engine, alternator and panel should be one integrated unit mounted on skids
Connection to ground:
The generator is supplied with connection to ground system comprising low resistance rod(s), terminals, cables, etc